INSTRUCTION FOR USE - cylinder-regulators.com CHECK IT OUT close
Home » EMU MAINTENANCE VALVE

EMU MAINTENANCE VALVE

The VSP valve is used as third source to feed the network that distributes gases; it is used in case of maintenance of both the control board for medical gas central station and the emergency control board for medical gas central station.

The STANDARD model of VSP valve has an UNI or AFNOR or NIST (5359) outlet according to the customer’s requirements; under the central body of the valve we put a valve that allows to scavenge automatically the gas in case there is too much pressure (over-pressure valve).Standard pressure switch high/low pressure is included.

When we connect the VSP valve, we also install a low pressure gauge connected to the alarm of the central station. This gauge gives the possibility to check the value of the pressure inside the system.

Item No. Gas Inlet point
VALV01V O2 Afnor
VALV02V Air Afnor
VALV03V N2O Afnor
VALV04V N2 Afnor
VALV05V CO2 Afnor
VALV06V O2 Uni
VALV07V Air Uni
VALV08V N2O Uni
VALV09V N2 Uni
VALV10V CO2 Uni
VALV15V O2 Nist
VALV16V Air Nist
VALV17V N2O Nist
VALV18V N2 Nist
VALV19V CO2 Nist

TECHNICAL DATA

Standard pressure in p1: 8 bar (800 kPa) 
Flow rate:  >20 m3/h 
Valve material: Brass alloy P-CuZn40Pb2 (sn 355N/mm2)
Production: Turning brass
Surface treatment:  0.25 mm Chromed surface
Leakage absences test pressure:  11.2 bar
Seal test:  No leakge
Discharge rate: >25 m3/h  
Inlet pipe: Set for pipe Ø16 ext.
Outlet pipe:  Set for pipe Ø16 ext.
Welding alloy: DIN 8513 (BS. 450 Sn)
  Ag 46%, Cu 27%, Zn 24%, Sn 3%, Cd 0%
Over pressure valve characteristics:  
Inlet connection: M14x1.5 (inlet joint)
Outlet connection: M22x1.5 (outlet joint)
Pressure in p1: 8 bar (800 kPa)
Over pressure test valve: 12.8 bar
Leakage result at 1.6 P1: no loss of pressure
Drain flow rate: > 97 m3/h